Generators / 12 lead 3 phase to single phase TR2 zig zag or double delta
« on: January 30, 2012, 08:53:42 PM »
Back in 2007 I got a used TR2 10KW 12 lead Lima marathon 3 phase generator from dieselgman, rebuilt the top end and rewired it to zig zag for 120/240 single phase.
Last week had a 66 hour run from the Ice storm, in Western Washington. It wet stacked towards the end, not loaded enough, so have been doing some searches and found the double delta schematic for single phase. Would that be any better than zig zag for loading.
Thanks Larry Harter
Last week had a 66 hour run from the Ice storm, in Western Washington. It wet stacked towards the end, not loaded enough, so have been doing some searches and found the double delta schematic for single phase. Would that be any better than zig zag for loading.
Thanks Larry Harter